Common causes and treatments for failure to ignite gas boilers
May 07, 2021
Leave a message
In the process of using a gas boiler, ignition is required, and failure to ignite is also the most common fault. During the use of gas boilers, it is most likely to fail to ignite, causing the gas boiler to fail to work normally. The manufacturer of Bright Boiler will introduce you to several common reasons why gas boilers cannot ignite.
Common reasons why gas boilers can’t light up:
1. Igniter fault: If one of the pulse igniter and the controller fails, the gas boiler cannot be started. Set the boiler ignition pressure to be too high or too low, and it is no longer within the ignition range.
Treatment method: Check the boiler pressure to see if the pressure is within the ignition pressure range of the burner, and it can be operated in the control cabinet.
2. The gas inlet pressure is too low or too high, and the burner does not ignite.
Treatment method: check the inlet pressure gauge of the burner to see if the pressure is the same as the ignition pressure of the boiler
3. Water level problem: The filter screen at the water inlet of the gas boiler is blocked and the water cannot flow normally. The water level of the boiler is too low, lower than the ultra-low water level of the boiler, the boiler automatically interlocks, and the burner does not ignite
Treatment method: Check whether the boiler water level is lower than the ultra-low water level of the boiler, and clean the filter plug.
4. Solenoid valve fault: If only the ignition sound is heard when the gas boiler is ignited, and there is no "click" magnetic absorption sound of the solenoid valve, the solenoid valve may be damaged or aging, and the solenoid valve will be out of control when the ignition starts. It was able to pull in once, but it was on fire, but it was closed and then turned off. Before confirming the quality of the solenoid valve, it is necessary to confirm whether the igniter control circuit is normal. If there is a problem, the solenoid valve cannot be controlled to be closed. The combustion engine is unreasonable in debugging the gas and controlling the air distribution, and the combustion engine will automatically go out after ignition.
Treatment method: the ratio of gas and air adjustment is wrong, the air intake is too large, and the fire will be automatically extinguished after ignition
5. The natural gas leaks and the burner does not ignite.
Treatment method: Generally, burners have their own leak detection devices, which can be monitored by themselves.
Sixth, the smoke pipe cannot be exhausted normally. The gas boiler flue pipe is clogged, and the smoke pipe is too long to be installed correctly. Exhaust gas temperature is too high, boiler automatic interlock protection, burner does not ignite.
Treatment method: check the boiler exhaust gas temperature to see if it is higher than the boiler shutdown gas temperature
Seven, water-gas linkage installation problems: the tympanic membrane in the water-gas linkage valve of the gas boiler is aging or damaged, and the micro switch cannot be promoted; the micro switch is broken.
8. The boiler emergency stop switch is operated by mistake, and the burner does not ignite (the boiler does not operate)
Solution: At this time, generally all functions cannot be used, and you can monitor by yourself.