Precautions for the use of explosion-proof high-energy igniter 1. When connecting the high-energy igniter and the electric nozzle with a touch cable, make sure that the electrical levels on both sides of the cable and the middle of the igniter and electric nozzle are inseparably touched. Otherwise, it may damage the electrical connection or the igniter.
2. The transformer is a unique design scheme for the on-time and off-time working hours system. After 30 seconds of continuous ignition, it must be stopped for 60 seconds before re-ignition, otherwise it may cause damage to the high-energy igniter components.
3. The high-energy igniter is not allowed to be connected to the power supply when the output end is not connected to the electric nozzle, so as to prevent damage to the components.
Fourth, the high-energy igniter is 20 joules, the output voltage is 2500 volts, and an excellent grounding system is required during installation.
5. If when the switching power supply is connected, all normal condition indicator lights should be on. The complete system software of the explosion-proof high-energy igniter is composed of the high-energy igniter, high-voltage cables, conductive rods, and semiconductor material electric nozzles. So, how to maintain the explosion-proof high-energy igniter? Maintenance of explosion-proof high-energy igniter First, if the electric nozzle is not working, it should be withdrawn from the flame area to prevent its burning, deformation or damage.
Secondly, it is necessary to prevent water seepage or excessive dampness in the igniter, and clean up immediately when there is too much dust. Once again, the conductive poles and electric nozzles are made of high-alumina porcelain insulation. Drops and collisions are prohibited to prevent damage to the components of the insulation layer and endanger all normal applications.